EPC Power Corp. inverters · Hybrid-listed

EPC Power Corp. 50-100181 is a hybrid-listed inverter on California's eligible inverter list in 3 voltage options: 1,044.2–1,504.9 kW continuous output and 98–99% weighted efficiency at 480, 600, and 690 V. Listed since Sep 3, 2024.

Recorded installations

Systems matched to this model
5
Installation years
2020–2025
States represented
1

Counts cover matched records in a partial US sample. One system can name more than one model. They do not measure reliability or current sales.

Listed figures by voltage option

California's eligible inverter list restates manufacturer-submitted test results. These are not independent measurements of a unit in a home.

50-100181 {480V}

50-100181 {480V} listed figures
AC voltage (V)480
Continuous output (kW)1,044.2
Weighted efficiency (%)98
Night draw (W)291.17
Output at 40°C (kW)Not stated
Test DC voltage, minimum (V)720
Test DC voltage, nominal (V)1,110
Test DC voltage, maximum (V)1,500
Supplement SB flagYes
Grid profile flagY*
Listing dateSep 3, 2024
Efficiency across test conditions
Efficiency (%) by DC test voltage and output load
DC test voltage10% load20% load30% load50% load75% load100% load
Minimum97.909898.585298.635898.457298.088497.6996
Nominal97.985498.605698.586498.319497.89797.4388
Maximum95.767497.493897.834497.936497.685697.3356

50-100181 {690V}

50-100181 {690V} listed figures
AC voltage (V)690
Continuous output (kW)1,504.9
Weighted efficiency (%)98.5
Night draw (W)250.08
Output at 40°C (kW)Not stated
Test DC voltage, minimum (V)1,100
Test DC voltage, nominal (V)1,330
Test DC voltage, maximum (V)1,500
Supplement SB flagYes
Grid profile flagY*
Listing dateSep 3, 2024
Efficiency across test conditions
Efficiency (%) by DC test voltage and output load
DC test voltage10% load20% load30% load50% load75% load100% load
Minimum98.08520798.42309298.60121298.61693498.42482498.152387
Nominal97.91060898.34370298.56076198.55043698.36819198.057858
Maximum97.53181398.11671698.39238698.48463998.30782898.046349

50-100181 {600V}

50-100181 {600V} listed figures
AC voltage (V)600
Continuous output (kW)1,304.151
Weighted efficiency (%)98.5
Night draw (W)248
Output at 40°C (kW)Not stated
Test DC voltage, minimum (V)925
Test DC voltage, nominal (V)1,225
Test DC voltage, maximum (V)1,500
Supplement SB flagYes
Grid profile flagY*
Listing dateSep 3, 2024
Efficiency across test conditions
Efficiency (%) by DC test voltage and output load
DC test voltage10% load20% load30% load50% load75% load100% load
Minimum98.053298.72598.78898.67498.399698.0802
Nominal97.317698.468698.605498.549298.239497.8678
Maximum97.38998.293898.47998.422898.155297.8514

Maker or retailer figures